8 Years Exporter Kyn28A-24 Armored Removable AC Metal Enclosed switchgear

Short Description:

XGN66-12 fixed metal-enclosed switchgear  is used for receiving and distributing electric energy in 3.6, 7.2, 12kv three-phase AC 50Hz systems, suitable for frequent operation occasions, and its busbar system is a single busbar (and can be derived single bus with bypass and double bus structure). The switchgear meets the requirements of the national standard IEC60298 (3-35kv AC metal-enclosed switchgear) and has two proposed “five-proof” locking functions.


Product Detail

Product Tags

Overview

This equipment is indoor metal armoring w ith drawable switchgear(hereafter refer to as switchgear.3.6-12 kilovolt three phasc AC50Hz single bus bar and the single bus bar section system’s omplete eletricity distribution euipment is used in the power plant,small and medium-sized penerator nower transmission,industryand mining business power distbution as well as electrical industry svstem’s seconc transformer substation’s electric take-over,power transmission and large-scale high pressure motor starting and so on.The purpose is to control,protect and monitor.This switch equipment is up to the standard oflEC 298GB3906 and can prevent the charge from pushing and pulling the breaker,fom opening and closing the breaker,from insulation with electricity by mistaken,from earthed switch closing the breaker, from opening the switchs interlock when it with eletricity mistakenly.It can not only use with VS1 vacuum circuit breaker, but with ABB Corporation’s VD4 vacuum circuit-breaker.It is indeed a kind of power distribution euipment with superior performance.

Produnct Photos

Use environmental conditions

l.Normal condition:
a.Surrounding air temperatre:-10℃~+40℃;

b.Altitude:<1000M:

c.Relative environment humidity:The daily relative average humidity≤95%,the monthly relative average humidity≤90%;

d.Earthquake:8degree;

e.The surrounding air without corrosive or flammable gas or water vapour;

f.Without a lot of dirtiness and regular fierce vibration,under the severe condition,the intensity meets the first kind requirement.
2.Special working conditions:
Nole:Please negotiate with us if your product is used bevond the range of above condition.

The main technical parameters

Name Unit Data
Mafched breaker
ZN63A-12(VS1) VD4
Rated voltage kV 12 12
1 min power frequency endurable voltage kV 42 42
Rated impulse withstand voltage(peak value) kV 75 75
Rated frequency Hz 50 50
Rated current A 630、120、1600、2000、2500、3150、4000、5000
Rated current of branch busbar A 630、120、1600、2000、2500、3150、4000、5000
Rated short time withstand current(virtual value) kA 16、20、25、31.5、40、50 16、20、25、31.5、40、50
Rated peak endurable voltage kA 40、50、63、80、100、125 40、50、63、80、100、125
rated short-circuit duration s 4
Protection level The shell is IP4X,and IP2Xwhen compartment door and handcart door are opened
Weigh kg 700~1200 700~1200

Structure introduction

The switch equipment is designed according to GB3906-91metal amoring seal switch equipmnent.The rectifier bocy is made up of the cabinet body and draw-out parts(namely handcart placed in the middle.See charter1.The cabinet divides into four separate rooms, the outer covering protection grade is IP4Xwhen each small room and the circuit breaker is openedthe protection grade is IP2X. It can suspend the inlet,outlet ine.cables inlet.outlet line and other function plan.After arranged and combinedit can beome each kind of plan form of the power distribution equipment.This switch equipnent may be installed and maintained from the frontage,therefore it may compose the dul arrangement back to back and be installed against the wall,improving the switch equipment’s security and flexibility and making full use of the occupying area.

Switchgear structure diagram

A. the bus bar room
B. the circuit breaker handcart room
C. the cable room
D. the relay instrument room

1.cover
2.branch small bus bar
3.bus bushing
4.main bus bar
5.statie contact device
6.contact box
7.current mutual induction current fransfor
8.earthed switch
9.cable
10.arrester
11.earthed main bus bar
12.mother board
13.control the small bus bar
14.earthed switch operating mechanism
15.draw-out horizontal clapboard
16.heafing device
17.circuit breaker handcart
18.scondary plug
19.clapboard(valve)
20.loading and unloading clapboard
21.pressure release channel

Switchgear Dimensions

A Handcart

The framework of handcart is made of steel sheet through the procession of CNC machine tool and rivet welding.According to the application.the handcarts can be divided into circuit breaker handcart,voltage transformer handcart,isolating handcart and metering handcart,etc.The handcarts of the same specification can be exchanged conveniently. In the cabinet,the handcart has isolating position, testing position and operating position,each of which is designed with alocation device to assure that the handcart can’t move easily at the above-mentioned positions.while the interlock must be unlocked to move the handcart

B Bus chamber

The busbar is led from one switch cabinet to another one and fixed with static contact box through branch bus.The flat branch bus is connected through the bolt to the static contact box and main bus.not needing any other line clamps or insulators.When there is speciademand of the clients or the project,the connecting bolt on the bus bar can be encapsulated with insulation and end cap.When the bus cosses the baffle of the switch cabinet,fix it with bus bushing,so that,if there is any interal fault arc,it can prevent the fault spreading to another cabinet and can guarantee the mechanical strength of the bus.

C Cable chamber

Inside the cable chamber,the current transformer,grounding switch arrester and cable can be installed,and on the bottom is designed slotted removeable aluminum sheet to assure the convenient site construstion.

D Relay instrument chamber

Relay instrument chamber is usd to installall kinds of components,such asrelays.instruments,signal indicator and operating switch, ect. In addition, it’s available to add a smallbus chamber on the top of the instrument chamber according to the demand of the clients, and set 16 lines to control the small bus.

Pressure releasing device

On the handcart chamber,bus chamber and cable chamber is installed pressure releasing device.When there is internal fault are in the breaker, main bus or inside the cable chamberand with the appearance of electric arethe intenal pressure in the switch cabinet rises. After it rises to acertain pressure,the pressure releasing metal sheet of the top device will be opened automatically,and the pressure and the gas are released to guarantee the safety of the operator and the switch cabinet.

Laeching device

Latching device is used to connect the central exit and cabinet body,and the lifting device is also designed to make i more convenient to open the central exit.When the central exit stays closed,the connecting strength with the cabinet body is the best and the capability against the internal arcing fault effectively is strengthened.


  • Previous:
  • Next:

  • Related Products