Wholesale ODM Zg6 Series Sf6 Metal Enclosed Gas Insulation Switchgear (C-GIS) Vvvv+Kvvvv

Short Description:

XGN-12 series unit type AC metal closed ring network high voltage switchgear electrical cabinet  is a fully insulated, fully sealed, and maintenance-free solid insulated vacuum switchgear. All high-voltage live parts are molded with epoxy resin material with excellent insulation performance, and the vacuum interrupter, main conductive circuit, insulating support, etc. are organically combined into a whole, and the functional units are connected by a fully insulated solid busbar. Therefore, the entire switchgear is not affected by the external environment, and the reliability of the operation of the device and the safety of the operator can be ensured. Because the product has the advantages of full insulation, full sealing, and full shielding, it is especially suitable for use in areas with high altitude, high temperature, mixed heat, severe cold, and severe pollution.


Product Detail

Product Tags

Overview

KYN61-40.5(2)type altermating current metal-clad and meta-enclosed with drawable switchgear (hereinafter referred to as switchgear) is a indoor complete set of power distribution unit of three-phase AC50Hzand rated voltage of 40.5kV.Used for receiving and distributing the eleetric energy in power plants,transformer substations,mining and industrial enterprises,etc. it controls,protects and detects the circuits also is applicable to freauent operation locations.This swichgear complies with GB/T11022-1999,GB3906-1991,DL404-1997,etc.

Main feature

◇Cabinet structure is of assembled type,the circuit breaker adopts floor type handcart structure;
◇Equipped with brand new composite insulated vacuum circuit breaker,is featured with good interchangeability,and is simple to change;
◇The handcart frame is mounted with lead screw nut propelling mechanism,it is able to move the handcart easily,and prevent damage ol propelling mechanism caused by misoperation;
◇All operations can be carried out when the cabinet dooris closed;
◇Interlocking among the main switch,handcart and switchgear adopts compulsory mechanical locking mode, meeting the”five preventions”function;
◇Cable chamber is large enough,it could connect multi cables;
◇The fast earthing switch is used for earthing and circuit short-circuit;
◇Of protection of the enclosure is P3Xand isIP2X when the door of handcartchamber is opened;
◇The product complies with GB3906-1991DL404-1997and refers to IEC-298.

Use enviromental conditions

◇Ambient temperature:-10°C-+40℃,average value measured within 24h should not exceed35℃;
◇Altitude:≤1000m;
◇Relative humidity:daily≤95%.monthly≤90%;
◇Seismic intensity:≤s8;
◇Vapor pressure:daily<2.2kPa,monthly<1.8kPa;
◇Ambient environment: the installation site should be free of fire,explosive danger,serious pollution,chemical corrosion or severe vibration.

Vacuum breaker switchgear main technical parameters

Name Unit Value
Rated voltage KV 40.5
Rated current A 1250 1600 2000
Rated frequency Hz 50
Rated short-time withstand current KA 20 25 31.5
Rated peak withstand current KA 50 63 80
Rated power frequency withstand voltage KV 95/1min
Rated lighting impulse withstand voltage KV 185
Rated short-circuit duration S 4
Degree of protection IP3X

Vacuum circuit breaker main technical parameters

Name unit value
Rated voltage kV 40.5
Rated frequency Hz 50
Rated power frequency withstand voltage kV 95/1min
Rated lighting impulse withstand voltage kV 185
Rated current A 1250 1600 2000
Rated short-time withstand current kA 20 25 31.5
Rated short-time breaking current kA 20 25 31.5
Rated peak withstand current kA 50 63 80
Rated short-circuit duration ms 4
Opening time ms 30≤t≤60
Closing time s 50≤t≤100
Rated short-circuit breaking current times times 20
Protection Level times 10000

Spring operating mechanism main technical parameters

Name Unit value
Rated operating voltage Opening coil V DC220/110,AC220/110
Closing coil
Rated operating current Opening coil V 0.96(220V),1.05(110V)
Closing coil
Power of energy-storage motor W 230
Rated voltage of energy-storage motor V DC220/110,AC220/110
Energy-storage time S ≤12

Switchgear structure features

Outline dimension of switchgear

outline dimension(W×D×H)

1400×2800×2600

Structural schematic diagram of switchgear

A relay meter B bus chamber C ciircuit breaker D cable chamber

 

Switchgear

Schematic diagram of installation foundation of switchgear

a:Height of electrical room:≥4500mm;

b:Distance between cabinet back and wall:≥1500mm;

c:Flatness of foundation frame:≤1mm/m2;

d:The height of embedded channel steel of foundation shall not exceed 3mm above the ground;

e:It can be fixed on the foundation by bolts or welding;

f:The weight of switch cabinet is about 1800kg

g:The width of switch cabinet operation corridor(single row):≥3000mm;double face(face to face)≥4000mm.

Tranformer performance parameters

Primary wiring schemes of switchgear include 27 typical schemes,meeting users’ demands on cable incoming and outgoing lines,overhead incoming and outgoing lines tie,measurement and protection,if requine other schemes,required please conta with ct the manufacturer.

s