XGN-12KV Unit Type AC Metal Closed Ring Network High Voltage Switchgear Electrical Cabinet
Model Description
The main technical parameters
Item | Unit | Parameters |
Rated voltage |
KV |
12 |
Rated frequency |
Hz |
50 |
Max rated current of main busbar and fuse |
A |
630/125 |
Max rated current of main bubar and fuse rated short time withstand current of main |
KA/S |
20/3 |
Main loop earthed loop max endurable rated current rated withstand current of main loop |
KA |
50 |
Main loop earthed loop short circuit on and off rated current rated short circuit on -off current of main time withstand current of main |
KA |
50 |
The opening times of the load switch with full capacity |
Times |
100 |
The fused breaker opening the current breaking current of fuse |
KA |
31.5 40 |
Rated closed loop breaking current |
A |
630 |
Rated shift current |
A |
1600 |
Machine life mechanical life |
Times |
2000 |
1min line frequency resistance (Peak value) recurrence to the earth/isolation fracture |
KV |
42/48 |
Light impulse withstand voltage(Peak value)recurrence to the earth /isolation fracture |
KV |
75/85 |
Secondary loop 1min power frequenly withstand voltage |
kv |
2 |
Protection level |
IP3X |
Product structure features
Solid insulated fully enclosed switchgear: It is a single or combined main conductive circuit such as isolating switch, grounding switch, main busbar, branch busbar, etc., which is made of solid insulating material as the main insulating medium and conductive connection, and then wrapped and encapsulated with solid insulating medium. Or several modules with certain functions, which can be combined or expanded again with full insulation and full sealing performance. The three-position mechanism adopts an over-center spring design, which has the function of breaking and closing the load current, and can also realize manual and electric operation.
Environment condition
1. Ambient air temperature: -5~+40 and the average temperature should not exceed +35 in 24h.
2. Install and use indoors. Altitude above sea level for operation site should not exceed 2000M.
3. Relative humidity should not exceed 50% at max temperature +40. Higher relative humidity is allowed at lower temperature. Ex. 90% at +20. But in view of the temperature change, it is possible that moderate dews will produce casually.
4. Installation gradient not exceed 5.
5. Install in the places without fierce vibration and shock and the sites insufficient to erode the electrical components.
6. Any specific requirement, consult with manufactory.